14.2 To activate/deactivate the timer
1. Starting from the Main screen (see section 4.2):
- press the key Menu (F1)
- press the key until the option Modify Params is followed by a horizontal arrow
- press the tabulator key (2) to activate the menu
2. Use the key to scroll until the option Clock function is followed by a horizontal arrow. Press the
tabulator key (2); following screen appears:
Clock Function
Not activated
Menu Mod Del
F1 F2 F3
3. Press the key Mod, <<Not activated>> starts blinking.
4. Press the key, <<Not activated>> changes into <<Activated>>.
5. Press the key Prog.
Important:
1. It is necessary to program the start/stop/pressure band commands in successive order timewise,
e.g.:
07.30 start
07.30 band 1
08.30 band 2
17.00 stop
etc.
2. Make sure that the clock function is activated (indicated as <<Activated>>). If not, the
programmed start/stop commands will not be executed.