Programming compressor control modes
Compressor control modes
The compressor can be controlled locally, remotely or via a local area network (LAN-consult Atlas
Copco).
Procedure
1. Starting from the Main screen (see section 4.2):
- press the key Menu (F1)
- press the key until the option Modify Params is followed by a horizontal arrow
- press the tabulator key (2) to activate the menu
2. Use the key to scroll until the option Configuration is followed by a horizontal arrow.
3. Press the tabulator key (2): The first option shown is <<Time>>. Scroll through the display (using
or keys) until the option C.C.M. is followed by a horizontal arrow and select it using the
tabulator key (2). Following screen is shown:
CCM
Local control
Menu Mod
F1 F2 F3
Fig. 15.1 Compressor control mode menu
4. Press the key Mod and use the or keys to select the desired control mode. Press the Prog
key to program or the Cancel key to cancel the modification.