Instruction manual
Preliminary 45
Consult the preventive maintenance schedule (section 5.1) for
replacing intervals.
Drain condensate from the primary fuel filters (water separators)
regularly by loosening the drain plugs (4). Catch the condensate in
a drain pan. Tighten the plugs after draining.
5.6.2 C18 electrical fuel priming pump
instruction
Switch unit ON
Place the end of the transparent fuel hose in a suitable container to
catch fuel when priming
Turn yellow valve (a) on priming pump to the open position
Activate the priming pump by switching (b) to the ON position
Switch off (b) when fuel appears in the transparent hose
Close valve (a) and drain fluid left in transparent hose
Start the engine and initiate a test run
5.6.3 Cleaning fuel tanks
To drain sediment and water from the fuel tanks (1), remove the
drain plug (2) of both fuel tanks and frame.
For a better drainage slightly slope the unit.
Use water to clean the inside of the fuel tanks, use a high-pressure
purifier if necessary. Spurt the sediment and water to the drain side
of the tank.
5.7 Cleaning coolers
Keep all coolers clean to maintain the cooling efficiency.
The fan side surface of the radiator, intercooler, aftercooler 1 and
oil cooler is accessible by opening the service doors.
The CAC/fuel cooler and aftercooler 2 are located at the rear end of
the unit, under the air filters.
Remove any dirt from the coolers with a fibre brush. Never use a
wire brush or metal objects. Then clean by air jet in reverse
direction of normal flow.
If the dirt is oily, wash the coolers with fuel or a cleansing agent.
A spray gun should preferably be used to apply the solvent to the
cooler block. Rinse the block by means of a water jet after a
soaking-in period. Steam-cleaning may also be applied.
Close the service doors.
Do not leave liquids behind.
If pump does not start when switch (b) is activated,
check fuse in CCM fuse box
3
!
After cleaning or heavy rains, drain the spillage-free
frame.
Protect the electrical and controlling equipment, air
filters, etc. against penetration of moisture.
2
1
!
!