DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
No signal (reserved)4
Warning: The voltage of the RTC button cell is too low.1(126) = "Bit: RTC button
cell"
Bit: RTC button cell
5
No signal0
The real time clock has not yet been set on the basis of
valid values.
1(77) = "Bit: RTC not set"
Bit: RTC not set
6
No signal0
Warning: Configuration setting is incorrect.
The device can still be operated with restrictions.
1(108) = Bit: Config. Warn-
ing
Bit: Config. warning
7
No signal0
Byte 19:Warnings 3
Table 16: Byte 19: Warnings 3
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
Warning: FO cable system reserve reached (critical or
permissible Rx receive level)
1(111) = Bit: Wrn FOC
budget
Bit: Wrn FOC budget
0
No signal0
Warning:
Optical receiving signal (channel 1) incorrect (no or insuf-
ficient Rx receive level) or RS-485 format error (incorrect
bit(s))
1(83) = "Bit: Wrn FO loop"
Bit: Wrn FO cables
1
No signal0
Warning: Loss of signal analogue input 21(92) = "Bit: Wrn input AIN
2"
Bit: Wrn input AIN 2
2
No signal0
Warning: Loss of signal analogue input 11(91) = "Bit: Wrn input AIN
1"
Bit: Wrn input AIN 1
3
No signal0
Collective signal 15: Internal warning1(70) = "Bit: Internal warn-
ing"
Bit: Internal warning
4
No internal warning0
Warning: Max. number of motor starts (starts) exceeded1(85) = "Bit:WrnOnTiStarts"
Bit: WrnOnTiStarts
5
No signal0
Warning: Max. running time/h exceeded1(84) = "Bit: WrnOnTiRun-
ning"
Bit: WrnOnTiRunning
6
No signal0
Warning: Max. permissible operating time for an operation
(OPEN-CLOSE) exceeded
1(63) = "Bit: Operat. time
warning"
Bit: Op. time warning
7
No signal0
Byte 20:Warnings 4
Table 17: Byte 20: Warnings 4
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
No signal (reserved)0
No signal (reserved)1
Warning: Loss of signal of actuator setpoint position1(95) = "Bit: WrnSetpoint-
Pos"
Bit: WrnSetpointPos
2
No signal0
Warning: A Partial Valve Stroke Test (PVST) should be
performed.
1(208) = "PVST required"
Bit: PVST required
3
0
Warning: FO cable connection not available.1(127) = "Bit: Wrn FOC
connection"
Bit: Wrn FOC connection
4
No signal0
The failure behaviour is active.1(30) = "Bit: Failure behav.
active"
Bit: Failure behav. act.
5
No signal0
29
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA AUMATIC ACExC 01.2 and is the answer not in the manual?

AUMA AUMATIC ACExC 01.2 Specifications

General IconGeneral
BrandAUMA
ModelAUMATIC ACExC 01.2
CategoryController
LanguageEnglish

Related product manuals