EasyManua.ls Logo

AUMA SA 10.2 - Checking Direction of Rotation (Hollow Shaft;Stem); Limit Switching Check

AUMA SA 10.2
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.6.2. Direction of rotation at hollow shaft/stem: check
Figure 69: Direction of rotation of the hollow shaft/stem for operation in direction
CLOSE (clockwise closing version)
[1] Threaded plug
[2] Seal
[3] Hollow shaft
[4] Protective cap for stem protection tube
[5] Stem
[6] Stem protection tube
Valve damage due to incorrect direction of rotation!
If the direction of rotation is wrong, switch off immediately (press STOP).
Eliminate cause, i.e. correct phase sequence for cable set wall bracket.
Repeat test run.
Check direction of rota-
tion
1. Move actuator manually to intermediate position or to sufficient distance from
end position.
2. Depending on the version: Unscrew threaded plug [1] with seal [2], protective
cap [4] or stem protection tube [6].
3. Switch on actuator in direction CLOSE and observe direction of rotation at hollow
shaft [3] or stem [5]:
The direction of rotation is correct if the actuator moves in direction CLOSE
and the hollow shaft in clockwise direction, or the stem moves downward.
4. Correctly fit/screw on threaded plug [1] with seal [2], protective cap [4] for stem
protection tube [6], fasten thread.
9.6.3. Limit switching: check
1. Set selector switch to position Local control (LOCAL).
65
SA 07.2 SA 16.2 / SAR 07.2 SAR 16.2 Control unit: electronic (MWG)
AC 01.2 Non-Intrusive EtherNet/IP Commissioning (basic settings)

Table of Contents

Other manuals for AUMA SA 10.2

Related product manuals