Figure 10: Signal: Safety function active
Information
As soon as a safety function is active (SIL function active indication), the actuator is
controlled via the safety PLC and the SIL module. For normal control (standard
PLC), controls are therefore Not ready REMOTE.
6.2. SIL configuration warning
In combination with the safety functions, the following configurations or settings of
standard controls may have an impact on the standard functions:
Self-retaining Local M0076 = OPEN/CLOSE
Self-retaining Remote M0100 = OPEN/CLOSE
If one of these configurations is selected in the standard controls, the device generates
the SIL config. warning.
6.3. Backlight
In standard operation, display backlight of actuator controls is white. In the event of
a fault, the display backlight is red. The red backlight does NOT refer to the safety
function status but to the faults referred to as "faults" in the Manual (Operation and
setting) AUMATIC AC 01.2.
19
Multi-turn actuators
SA 07.2 SA 16.2/SAR 07.2 SAR 16.2 Indications on display