AUMA SAR 07.6 - Test;Replace Fuses F3;F4; Motor Protection (Thermal Monitoring)

AUMA SAR 07.6
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Features and functions
Auxiliary voltage 24 V DC: max. 100 mA for supply of control inputs, galvanically isolated
from internal voltage supply.
Standard:Voltage output
Auxiliary voltage 115 V AC: max. 30 mA for supply of control inputs, galvanically isolated
from internal voltage supply
(Not possible in combination with PTC tripping device)
Option:
2 analogue outputs:
With position transmitter option: Output of travel and torque as continuous values between 0/4 and 20
mA
Analogue output (option)
2 analogue inputs:
With positioner/process controller option: Input of actual position value/actual process value as continuous
values between 0/4 and 20 mA
Analogue input (option)
Selector switch: LOCAL - OFF - REMOTE (lockable in all three positions)
Push buttons OPEN, STOP, CLOSE, RESET
-
Local STOP
The actuator can be stopped via push button STOP of local controls if the selector
switch is in position REMOTE. (Not activated when leaving the factory.)
6 indication lights:
-
End position and running indication CLOSED (yellow), torque fault CLOSE (red),
motor protection tripped (red), torque fault OPEN (red), end position and running
indication OPEN (green), Bluetooth (blue)
Graphic LC display: illuminated
Standard:Local controls
Special colours for the indication lights:
-
End position CLOSED (green), torque fault CLOSE (blue), torque fault OPEN
(yellow), motor protection tripped (violet), end position OPEN (red)
Option:
Bluetooth class II chip, version 2.1: With a range up to 10 m in industrial environments, supports the
SPP Bluetooth profile (Serial Port Profile).
Required accessories:
AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC)
AUMA Assistant App (Commissioning and Diagnostic Tool for Android devices)
Bluetooth
Communication interface
Selectable type of seating, limit or torque seating for end position OPEN and end po-
sition CLOSED
Torque by-pass: Adjustable duration (with adjustable peak torque during start-up time)
Start and end of stepping mode as well as ON and OFF times can be set individually
for directions OPEN and CLOSE, 1 to 1,800 seconds
Any 8 intermediate positions: can be set between 0 and 100 %, reaction and signal
behaviour programmable
Running indication blinking: can be set
Positioner
-
Position setpoint via HART interface
-
Programmable behaviour on loss of signal
-
Automatic adaptation of dead band (adaptive behaviour selectable)
-
Split range operation
-
Change-over between OPEN-CLOSE control and setpoint control possible via
HART interface
Standard:Application functions
PID process controller: with adaptive positioner, via 0/4 20 mA analogue inputs for
process setpoint and actual process value
Multiport valve: Up to 16 positions, signals (pulse or edge)
Automatic deblocking: Up to 5 operation trials, travel time in opposite direction can be
set
Static and dynamic torque recording for both rotation directions with torque measure-
ment flange as additional accessory
Options:
80
SA 07.2 SA 16.2/SAR 07.2 SAR 16.2 Control unit: electronic (MWG)
Technical data AC 01.2 Non-Intrusive HART