3.6. Applications (environmental conditions)
When specifying and using the actuators within safety instrumented systems, make
sure that the permissible service conditions and the EMC requirements by the
peripheral devices are met. Service conditions are indicated in the technical data
sheet:
Enclosure protection
Corrosion protection
Ambient temperature
Vibration resistance
If the actual ambient temperatures exceed an average of +40 °C, the lambda values
have to be incremented by a safety factor. For an average temperature of +60 °C,
this factor is specified to 2.5.
For environmental tests, actuator and actuator controls were subjected to the following
standards:
Dry heat: EN 60068-2-2
Damp heat: EN 60068-2-30
Cold: EN 60068-2-1
Vibration test: IEC 60068-2-6
Induced seismic vibration (earthquake): IEC 60068-3-3
3)
Enclosure protection test IP68: EN 60529
Salt spray test: EN ISO 12944-6
Immunity requirements: EN 61326-3-1
Emission: EN 61000-6-4
3) Thyristor version only
12
Part-turn actuators
Architecture, configuration and applications with AC 01.2-SIL/ACExC 01.2-SIL

Table of Contents

Other manuals for AUMA SQ 05.2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA SQ 05.2 and is the answer not in the manual?

AUMA SQ 05.2 Specifications

General IconGeneral
BrandAUMA
ModelSQ 05.2
CategoryController
LanguageEnglish

Related product manuals