12.3.2. Fuse replacement
12.3.2.1. Replace fuses F1/F2
Information: Only valid for version with electrical connection of KES type, KT
type or KL type
Electric shock due to presence of hazardous voltage!
Death or serious injury.
Disconnect device from the mains before opening.
1. Remove electrical connection from actuator controls.
Figure 88:
2. Pull fuse holder out of pin carrier, open fuse cover and replace old fuses by
new ones.
12.3.2.2. Test/replace fuses F3/F4
Information: For version with electrical connection type KP/KPH, the fuses
(F1/F2) are also located on the PSU board.
1. Loosen screws [1] and remove cover [2] on the rear of the actuator controls.
Figure 89:
Check fuses.
2. The power supply unit has measuring points (solder pins) allowing to perform
a resistance (continuity) measurement:
Table 37:
Measuring pointsChecking
MTP1 MTP2F1
MTP3 MTP4F2
MTP5 MTP6F3
MTP7 MTP8F4
83
SQEx 05.2 SQEx 14.2/SQREx 05.2 SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Profibus DP Corrective action