Ethernet Communications Modules, 3rd Edition, Rev. D
A-3
Appendix A: General Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
H0-ECOM100
Module Type
Intelligent Data Communications Module
Quantity of Modules Per Base
Defined by CPU and base configuration
Diagnostics
LEDs/Network Monitoring Software (NetEdit3)
Communications
10/100BaseT Ethernet
Data Transfer
100 Million bits per second
Extension Port
RJ45
Link Good Indicator (LINK)
Green LED
Activity Indicator (ACT)
Green LED
Error Indicator (ERR)
Red LED
100MB Transfer Rate (100M)
Green LED
Power Consumption
300mA (Supplied by DL05/DL06 base)
Operating Temperature
32º to 140º F (0º to 60º C)
Storage Temperature
–4º to 158º F (–20º to 70º C)
Relative Humidity
30% – 95% RH (non-condensing)
Environmental Air
No corrosive gases permitted
Networking Protocols Supported
TCP/IP, IPX, Modbus TCP, DHCP, HTML Configuration
Manufacturer
Host Automation Products
Link Distance
100 meters (328 feet)
H2-ECOM100/H4-ECOM100
Module Type
Intelligent Data Communications Module
Quantity of Modules Per Base
Defined by CPU and base configuration
Diagnostics
LEDs/Network Monitoring Software (NetEdit3)
Communications
10/100BaseT Ethernet
Data Transfer
100 Million bits per second
Extension Port
RJ45
Status Indicator (STATUS)
(H2-ECOM100 only)
Green LED
Link Good Indicator (LINKGD)
Green LED
Activity Indicator (ACTIVE)
Green LED
Error Indicator (ERROR)
Red LED
100MB Transfer Rate (100MBIT)
Green LED
Power Consumption
300mA (Supplied by DL base)
Operating Temperature
32º to 140º F (0º to 60º C)
Storage Temperature
–4º to 158º F (–20º to 70º C)
Relative Humidity
30% – 95% RH (non-condensing)
Environmental Air
No corrosive gases permitted
Networking Protocols Supported
TCP/IP, IPX, Modbus TCP, DHCP, HTML Configuration
Manufacturer
Host Automation Products
Link Distance
100 meters (328 feet)