Ethernet Communications Modules, 3rd Edition, Rev. D
2–2
Chapter 2: Setup and Installation
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
ECOM Network Identifiers
This section describes network identifiers that can be assigned to the ECOM module. Each
module must be assigned at least one unique identifier to make it possible for PCs or other
ECOMs to recognize it on the network. Four methods of identifying the ECOM module give
it the flexibility to fit most networking schemes.
The four ECOM identifiers are:
Module ID
Name
IP (Internet Protocol) Address
Ethernet (MAC) Address
The first three are user-selectable. The last one is set at the factory. Each of the identifiers is
discussed in this chapter. If you have more than a few ECOMs on your network, consider
making a chart or spreadsheet of network IDs, as shown below:
The decision about which type of identifier to use is an important one. Much of the decision
depends on the requirements of your particular application. PC-to-PLC communications are
generally better accommodated with one type of identifier while PLC-to-PLC communications
require a different type. Ease of maintenance and troubleshooting also must be considered
before deciding which type to use.
The identifiers are used to link your PC to your PLC or one PLC to another PLC. The flexible
design of the module allows you to use different identifiers for different links to the same
module. This is particularly important if you require both PC-to-PLC and PLC-to-PLC
communications on the same network.
The following table summarizes Network Identifiers and their uses:
Ethernet (MAC) Address Module ID Name IP Address
00 E0 62 20 01 20
3 PumpStationTwo 192.168.100.005
00 E0 62 20 01 58
8 Effluent 255.255.255.255
00 E0 62 20 01 8D
17 BldgThree 192.168.100.001
00 E0 62 20 01 94
2 PumpStationOne 192.168.100.002
00 E0 62 20 01 DE
61 192.168.100.003
00 E0 62 20 01 F1
33 192.168.100.004
00 E0 62 20 01 FB
1 Control Room 255.255.255.255
00 E0 62 20 01 F0
5 Mixer 192.168.100.006
How to Set Format Communication Restrictions/Notes
Module ID
DIP Switch Number 1–63
PLC to PLC or
PC to PLC
Disables Module ID in
NetEdit3
NetEdit3 Number 1–90
DIP switch must be set
to “0”
NetEdit3 Number 1–999,999,999
PC to PLC only
>90 (Not for PLC to PLC)
Name
NetEdit3
32 Alphanumeric
Characters
HMI software may have
restrictions
IP Address
NetEdit3
4 Three-digit Numbers,
xxx.xxx.xxx.xxx
(See page 2-4)
PC to PLC; (PLC to PLC
- Client/Server using
TCP/IP or Modbus TCP
protocol)
See you network
administrator for IP address;
(refer to pages 3-10 to 3-11,
chapters 5 & 6)
Ethernet (MAC)
Address
Set at Factory 12 Hex digits PC to PLC only Factory assigned, for IPX