EasyManua.ls Logo

Automationdirect.com HX-ECOM Series - Network Server (Slave) Operation; Modbus Function Codes Supported; Determining the Modbus Address

Automationdirect.com HX-ECOM Series
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ethernet Communications Modules, 3rd Edition, Rev. D
5-5
Chapter 5: MODBUS TCP for H0/H2/H4-ECOM100
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Network Server (Slave) Operation
This section describes how other Modbus TCP clients on a network can communicate with an
H0/H2/H4 -ECOM100 that you have configured for Modbus TCP protocol. A network client
must send a Modbus function code and Modbus address to specify a PLC memory location
the DL05/06/205/405 CPU. No CPU ladder logic is required to support Modbus TCP server
operation.
Modbus Function Codes Supported
The H0/H2/H4 -ECOM100 supports the following Modbus function codes when acting as a
Modbus TCP server.
Determining the Modbus Address
There are typically two ways that most Modbus addressing conventions allow you to specify a
PLC memory location. These are:
By specifying the Modbus data type and address
By specifying a Modbus address only.
Modbus
Function Code
Function
DL05/06/205/405
Data Types Available
01 Read Discrete Output Table Y, C, T, CT
02 Read Discrete Input Table X, SP
03
Read Holding registers (when addressing mode
is 584/984, this function is used to access
analog output registers)
V
04
Read Input Registers (when addressing mode is
584/984, this function is used to access analog
input registers)
V
05 Force Single Discrete Output Y, C, T, CT
06 Preset Single Holding Registers V
08 Loop Back / Maintenance
15 Force Multiple Discrete Outputs Y, C, T, CT
16 Preset Multiple Holding Registers
V

Table of Contents