Planning
Technical Handbook, AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339, Revision 1, 2020-06-29,
Autronica Fire and Security
Page 43
8.3.2 Heat Detection
Note that if Operation Class Heat only is used, the guidance for heat
detection applies.
Ceiling height
Area of
coverage
Monitoring
distance
Under 6
meters
20 m
2
3,5 meters
Over 6
meters
Not permitted