AUX air conditioner service manual
34
Automatic wind-speed control
TA - TS3℃,wind-speed works in high wind;
TS +1TATS +3℃,wind-speed works in middle wind;
TATS1℃,wind-speed works in low wind;
Without 3 minutes delay when the wind speed turns from the high wind from the low wind, otherwise
with 3 minutes delay;
Being initially electrified, the compressor doesn’t have the 3 minutes extension/delay protection,
the outdoor fan starts after 2 seconds of the compressors start; TSTA set by the remote control, the
compressor turns off immediately with no need of 3 minutes delay protection;
Dehumidification mode
The four -way valve always turns off when the dehumidification mode is ongoing. The control range
of the temperature is: 16 - 32.
Under the dehumidification mode, after the 3 minutes protection conditions being meet
satisfactorily, the performance of the compressor and the outdoor fan is as following:
a)TA TS+2℃,the compressor and the outdoor fan works continuously, the wind speed retains the
setting wind speed;
b)TS TA < TS+2℃,the compressor and the outdoor fan runs for 10minutes and stops for
6minutesThe indoor fan turns off during the compressors 3 minutes stopping period and keeps on
working in breeze mode under other conditions;
c)TA < TSthe compressor and the outdoor fan stop working, and the indoor fan start to work in
breeze mode after stopping for 3 minutes
Automatic wind-speed control
TA - TS5℃,the wind speed is on high wind;
TS +3TATS +5℃,the wind speed is on middle wind;
TS +2TATS +3℃,the wind speed is on low wind;
TSTATS +2℃,the wind speed is on fitful breeze;
TATSthe indoor fan is off during the 3 minutes delay of the compressor, and 3 minutes later,
the wind is at breeze speed.
The primary electrifying to compressor has no 3 minutes protection delay, the outdoor fan starts 2
seconds later after the start of the compressor;
When the indoor fan runs, the horizontal air-blade can be set as free swing, and the swing condition
is same as the one under cooling mode
When TE TE1 last for 10seconds and the compressor runs continuously for above 5minutesif
turn off the compressor and outdoor fan, the indoor fan runs at the setting wind speed; If TE 7℃,
quit the protection
This mode includes the functions of timing, sleeping, auto-restart (optional), negative ion (optional),
I feeloptional.