AUX air conditioner service manual
34
⑧Automatic wind-speed control:
TA - TS≥3℃,wind-speed works in high wind;
TS +1℃≤TA<TS +3℃,wind-speed works in middle wind;
TA – TS<1℃,wind-speed works in low wind;
Without 3 minutes delay when the wind speed turns from the high wind from the low wind, otherwise
with 3 minutes delay;
⑨Being initially electrified, the compressor doesn’t have the 3 minutes extension/delay protection,
the outdoor fan starts after 2 seconds of the compressor’s start; TS>TA set by the remote control, the
compressor turns off immediately with no need of 3 minutes delay protection;
Dehumidification mode⑸
The four① -way valve always turns off when the dehumidification mode is ongoing. The control range
of the temperature is: 16℃ - 32℃.
②Under the dehumidification mode, after the 3 minutes protection conditions being meet
satisfactorily, the performance of the compressor and the outdoor fan is as following:
a)TA ≥ TS+2℃,the compressor and the outdoor fan works continuously, the wind speed retains the
setting wind speed;
b)TS ≤ TA < TS+2℃,the compressor and the outdoor fan runs for 10minutes and stops for
6minutes,The indoor fan turns off during the compressor’s 3 minutes stopping period and keeps on
working in breeze mode under other conditions;
c)TA < TS,the compressor and the outdoor fan stop working, and the indoor fan start to work in
breeze mode after stopping for 3 minutes;
Automatic wind-speed control:
TA - TS≥5℃,the wind speed is on high wind;
TS +3℃≤TA<TS +5℃,the wind speed is on middle wind;
TS +2℃≤TA<TS +3℃,the wind speed is on low wind;
TS≤TA<TS +2℃,the wind speed is on fitful breeze;
TA<TS,the indoor fan is off during the 3 minutes delay of the compressor, and 3 minutes later,
the wind is at breeze speed.
③The primary electrifying to compressor has no 3 minutes protection delay, the outdoor fan starts 2
seconds later after the start of the compressor;
④When the indoor fan runs, the horizontal air-blade can be set as free swing, and the swing condition
is same as the one under cooling mode;
⑤When TE ≤ TE1 last for 10seconds and the compressor runs continuously for above 5minutes,if
turn off the compressor and outdoor fan, the indoor fan runs at the setting wind speed; If TE ≥ 7℃,
quit the protection;
⑥This mode includes the functions of timing, sleeping, auto-restart (optional), negative ion (optional),
I feel(optional).