⑨Anti cold-wind and Residual-heat Removing function:
TE controls the wind speed of the indoor fan, and the specific conditions are as below:
●The anti cold-wind status when the compressor runs:
a) When TE in rise status and at the moment of TE<TE1,the indoor fan turns off;TE2≤TE<TE3,
the indoor fan blows the breeze; TE3≤TE<TE4,the indoor fan blows the mute wind; TE≥TE4,the
indoor fan blows the set wind speed;
b)When TE in fall status and at the moment of TE>TE5,the indoor fan blows the set wind speed;
TE6<TE≤TE5,the indoor fan blows the mute wind;TE7<TE≤TE6,the indoor fan blows the
breeze;TE≤TE7,the indoor fan turns off.
●The anti cold-wind status when the compressor stops working:
a)When TE is in fall status and at the moment of TE>TE2,the indoor fan blows breeze;at the
moment of TE≤TE2,indoor fan turns off;
b)When TE is in rise status and at the moment of TE≥TE6,the indoor fan blows breeze;at the
moment of TE<TE6,indoor fan turns off;
●The residual-heat Removing function:
When TE>TE8,the indoor fan runs in breeze,if ≤TE8,the indoor fan stops working, and the time in
removing residual heat ≤10seconds,Within the 10 seconds of residual heat removing, if TE< TE8, the