AUX air conditioner service manual
47
The setting temperature can be decided and adjusted by the remote control within the control range of
16℃ - 32℃ through the button of temp. Add “+” and temp. Reduce “-”. Press the button “wind speed
option” to choose the wind speed among the options of automatic fan, high fan, middle fan and mute
fan. The other conditions refer to the following:
⑴When TA-3-TS≤-1℃,if satisfying the 3 minutes protection delay condition for compressor, the
compressor and outdoor fan start, and the indoor fan runs in accordance with the anti-cold wind
condition.
W⑵ hen TA-3-TS≥1℃,if satisfying the 3 minutes protection delay condition for compressor,the
compressor and outdoor fan stop working, and the indoor fan runs in accordance with the anti-cold
wind condition.
⑶When TA-3=TS,remain the previous status;
⑷Temperature display has the temperature compensation of 3℃
A⑸ utomatic wind speed control:
TA < TS,run at high fan speed;
TS ≤ TA<TS +2℃,run at middle fan speed;
TA ≥ TS + 2℃,run at low fan speed;
There is no 3 minutes protection delay when the wind speed turns to high fan from the low fan; there
is 3 minutes protection delay when the wind speed turns to low fan from the high fan;
W⑹ hen heating process ongoing, the button of “Swing” can control the swing leaves to swing or
stop;
⑺Being electrified initially, the compressor has no 3 minutes protection delay. The compressor starts
10 seconds later after the start of the four-way valve, and the outdoor fan starts 2 seconds later after
the start of the compressor; Set the TS <TA-3 by remote control,the compressor stops immediately
and without the 3 minutes protection delay;
⑻This mode includes the timing function, sleeping function, auto-restart (optional), negative ion
(optional), I feel(optional).
⑼Being electrified initially, the four-way valve starts immediately ,and the compressor starts 10
seconds later; During the operation condition of the compressor, the four-way valve stops after
2min50s protection delay when stops the air-conditioner or switch mode;
In the case of compressor stops, the four-way valve stops immediately once stopping the
air-conditioner;
⑽Anti-cooling wind and residual-heat Removing function:
The wind speed of the indoor fan is controlled by TE, and the specific conditions are as below:
Anti-cold wind when compressor runs: