BL2 93317
Operating Manual 21
10 Technical Data
10.1 General data
Voltage AC 110 – 240 V , 50/60 Hz
Power consumption approx. 0.3 W
Terminal clamps 0.5 – 1.5 mm
2
, for solid one-wire conductors
Connection cable (recommended) NYM 5 x 1.5 mm
2
Circuit breaker max. 10 A
Detection area vertical 360°
Mounting height min./max./recom-
mended
2 m / 5 m / 2.5 m
Range (mounting height 2.5 m, at
ambient temperature 18 °C)
Walking across
Walking towards
Seated activity
max. Ø 8.0 m
max. Ø 4.8 m
max. Ø 3.2 m
Monitored area when moving across
the detector
50 m
2
at 2.5 m mounting height
Switch-on threshold 10 – 2000 Lux
Follow-up time 15 s – 60 min
Housing Polycarbonate, UV-resistant
Protection class / degree of protec-
tion
II / IP23
Dimensions H x Ø [mm] 63 x 80 mm
Ambient temperature -25 °C – +50 °C
Relay contact 1 x µ contact, normally open/NO
Switching capacity
1000 W, cos φ = 1
500 VA, cos φ = 0.5
200 W LED
remote controllable yes (with IR-BL)
Factory settings
Detection sensitivity
Follow-up time
Switch-on threshold
High
3 min
500 Lux
Nameplate