WWW.BALTIMOREAIRCOIL.COM
4
Rigging
RefertoTables 1, 2,and3 andFigures 1,6,and7foreachsection’srequiredminimum
spreaderbarlengthW1andW2(ifapplicable)andtherecommendedminimumvertical
dimension“H”.RefertoFigures 1,6,and7fordimensionreference.
Failuretouseliftingprovisionscanresultinadroppedloadcausingsevereinjury,death,
and/orpropertydamage.LiftsmustbeperformedbyqualiedriggersfollowingBAC
publishedRiggingInstructions,andgenerallyacceptedliftingpractices.Theuseofa
supplementalsafetyslingmayalsoberequirediftheliftcircumstanceswarrantitsuse,as
determinedbytheriggingcontractor.
NOTE: For weight information, refer
to the submittal drawing package.
Table 1. Minimum Vertical Dimension and Spreader Bar Length for Single Air Intake FXV and CXVB Units
Model Number Lower Section Upper Section
FXV CXVB H W1 W2 H W1 W2
FXV-0806x-x-x CXVB-x-0806-x
3'-6" 8'-6" 4'-0" 3'-1" 8'-6" 3'-2"
FXV-0809x-x-x CXVB-x-0809-x
4'-4" 8'-6" 4'-0" 3'-1" 8'-6" 3'-2"
FXV-0812x-x-x CXVB-x-0812-x
4'-4" 8'-6" 4'-0" 5'-3" 8'-6" 3'-2"
FXV-0818x-x-x CXVB-x-0818-x
5'-3" 8'-6" 4'-0" 8'-2" 8'-6" 3'-2"
FXV-1212x-x-x CXVB-x-1212-x
4'-4" 11'-10" 5'-3" 5'-3" 11'-10" 4'-2"
FXV-1218x-x-x CXVB-x-1218-x
5'-3" 11'-10" 5'-3" 8'-2" 11'-10" 4'-2"
NOTE: All single-cell and multi-cell
units must be rigged one section
at a time.
CROSSFLOW COIL PRODUCTS
Unit Rigging & Assembly
2
Figure 1a. Lower Section Lift
Section Assembly of Two-Piece Cells
Figure 1b. Upper Section Lift
WARNING: Failure to use lifting
provisions can result in a dropped
load causing severe injury, death,
and/or property damage. Lifts
must be performed by qualified
riggers following BAC published
Rigging Instructions, and generally
accepted lifting practices. The
use of a supplemental safety
sling may also be required if the
lift circumstances warrant its
use, as determined by the rigging
contractor.