INTERNAL EXTERNAL
External RESET BATCH input
11
Common ground unit
SIGNAL
8
GND
shielding
RESUME
SWITCH
+ 3.2V DC
1M
low-pass lter
Figure 12: External reset batch input
Terminal #08-12; Reset totalizer:
Use the RESET TOTALIZER function for end-of-shift coordination and control. You can reset the inventory totalizer to zero. The
input must be switched with a potential-free contact to the GND terminal #08 for at least 100 msec.
You can also use terminal #12 to block the RESET function from the keyboard: as long as this input is switched to terminal #08,
it is not possible to clear the actual totalizer. You must release the input to clear the total.
INTERNAL EXTERNAL
External RESET TOTALIZER input
12
Common ground unit
SIGNAL
8
GND
shielding
RESET
TOTALIZER
SWITCH
+ 3.2V DC
1M
low-pass lter
Figure 13: External reset totalizer input
Terminal #13-16; Transistor outputs T1, T2 and T3:
The function of these TRANSISTOR OUTPUTS is determined by SETUP functions 72-79.
The maximum driving capacity is 300 mA @ 50V DC per transistor.
Industrial Process Controller, Model PC200
Page 14 April 2017CTL-UM-00483-EN-07