23
4 IO-Link Interface
Analog
mode F0hex
The mode of the input ports can be set with this ISDU register.
Accessing the ISDU register through the subindex 0, the settings for all ports can be read/written.
Accessing the ISDU register through subindex 1-8, the port mode for the corresponding port
(P0-P7) can be read/written.
00
hex
= Voltage input, 0V - 10V
01
hex
= Current input, 4mA 20 mA
02
hex
= Voltage input, 5V 10V
03
hex
= Voltage input, -10V 10V
04
hex
= Voltage input, 0V 5V
05
hex
= Current input, 0mA 20 mA
06
hex
= Voltage input, -5V - +5V
07
hex
= Pt100
08
hex
= Pt1000
09
hex
= Type J thermocouple
0A
hex
= Type K thermocouple
FF
hex
= Port is switched off
Subindex 0:
Byte
0
1
2
3
4
5
6
7
Mode
Port 0
Mode
Port 1
Mode
Port 2
Mode
Port 3
Mode
Port 4
Mode
Port 5
Mode
Port 6
Mode
Port 7
Attention!
Changing the analog mode of the port to voltage or current input, +24V will be switched
between pin1 and pin 3, in order to supply the analog sensor. Be sure, that no Pt100 or
Pt1000 sensor is connected to the analog port. The +24V supply voltage can damage