Balluff Network Interface / IO-Link BNI IOL-719-002-Z012
www.balluff.com
Standard I/O-port (M12, A-coded, female)
+24 V, 150 mA (sensor supply)
GND (sensor supply, measurement)
Current Source 1 - / Analog In -
Current Source 1 - / Analog In -
Current Source 1 + / Analog In +
Current Source 1 + / Analog In +
Current Source 2 + / Analog In -
Current Source 1 + / Analog In +
Thermocouple Typ J, Typ K
Note
The +24V supply voltage is short circuit protected. The supply voltage will be
switched off in case of short circuit, in order to reduce the power dissipation. The
short circuit error is latched and it can be reset with the output process data.
Note
In case of current input, the BNI IOL-719-002-Z012 works only with 3-wire
sensors.