3.10.5 Mounting the Scanner and Adjusting the Angle
When mounting the brackets or scanner, do not exceed the listed torque or you will
damage the scanner. The pitch angle adjustment procedure applies to both uses of
the bracket assemblies.
The Positioning Memory Bracket (one piece) saves the inclination angle set for the
installation. This allows for quick installation without further mechanical adjustments
if it is ever necessary to replace the unit.
To mount the device with 90° vertical inclination:
1.
Mount the Positioning Memory Bracket (3) with the M4 screw (and washer)
(2) to the main bracket (1) but do not tighten it.
2. Align the Positioning Memory Bracket with the center of the main bracket
slot, then tighten the M4 screw (do not exceed 1.5 to 2 N·m torque).
3. Mount the scanner to the main bracket using the M5 × 12 Pitch Adjustment
Screws (with washers) (5) and the M5 × 12 Scanner Fastening Screws (4).
Tighten all four screws (do not exceed 2.5 to 3 N·m torque).
To place a device with a specific pitch angle:
1. Screw without tightening the M5 Scanner Fastening Screws, the M5 Pitch
Adjusting Screws, and the Positioning Memory Bracket with the M4 screw.
2. Rotate the device to the desired pitch angle within the allowed range (± 6°).
3. Tighten the M5 Scanner Fastening Screws and then the M5 Pitch Adjusting
Screws (do not exceed 2.5 to 3 N·m torque).
4. Tighten the Positioning Memory Bracket M4 screw (do not exceed 1.5 to 2
N·m torque).
Figure 36. Adjust the scanner angle
3.10.6 Adjusting the Roll Angle
The roll angle adjustment procedure only applies when all parts of
bracket SXA-MBK-1 are used. Rotate the brackets to reach the
desired roll angle within the allowed range (± 8.5°). Tighten the M4
Roll Adjusting Screws (7) (do not exceed 1.5 to 2 N·m torque) .
Figure 37. Adjust the roll angle
3.10.7 Scanner Mounting Safety Information
Verify the protection level assured by the
SX Series Safety Laser Scanner is compatible with the danger level of the working
machine, according to EN ISO 13849-1 or EN 62061.
Dangerous Machine Status:
• Verify the machine is off (not operating) during mounting, electrical installation, and commissioning.
• Verify the safety laser scanner’s outputs do not affect the machine during mounting, electrical installation, and
commissioning.
• Mounting and connecting the device must be carried out by qualified personnel only, according to the indications
included in the specific sections and in the applicable standards.
• Securely install the safety laser scanner so that access to the dangerous zone is not possible without passing
throughout the safety area. This must be done according to the indications included in the specific section and in the
applicable standards.
• Please carefully read the instructions for the correct functioning before powering the device.
Hazard due to safety device malfunctioning:
• If unsuitable brackets are used, the device may become damaged. Only use approved brackets for mounting.
• Personnel or parts of the body may not be detected in case of non-observance.
SX Safety Laser Scanner
44 www.bannerengineering.com - Tel: + 1 888 373 6767