CAUTION: The maximum input delay is based on the conveyor speed and package length. Set
the delay long enough to ensure only the package is passing through the curtain and short enough
to prevent inappropriate or unintended muting cycles.
7. Define the Timeout (minutes).
This parameter allows the entering of a muting backdoor timer (maximum time to stay muted). The default time limit is
10 minutes. The time limit can be increased from 10 minutes to 1080 minutes in 1 minute increments. For no time
limit, enter 0.
WARNING: Select an infinite time for the Muting Time Limit only if the possibility of an
inappropriate or unintended mute cycle is minimized as determined and allowed by the machine's
risk assessment. The user is responsible to make sure that this does not create a hazardous
situation.
8. Enable or disable Override.
If muting is enabled, an override function can also be enabled. The override allows OSSDs to be manually forced on
to drive an item out of the Safety Zone.
WARNING: Measures must be taken to prevent activation of the mute-depended override function
from a fault or inadvertent operation of the initiating device.
9. Set the Override Mode, if applicable.
The override mode can be selected as Single Line Pattern, Edge, or Level. See Mute-Dependent Override on p. 70
for details on these modes. A correct override input sequence forces the scanner's OSSD outputs ON. The
hazardous motion should not start until the initiation button (or hold to run switch) of the machine is also engaged.
The override time limit is 120 seconds.
10.
The Input Signals section, allows the configuration of the Multi In and unused Multi in/out pins depending on the
configuration's needs.
Reset—The reset input function can be added in Automatic or manual reset mode. The reset input allows
restoring normal operation after a failure lockout (fault) condition, due to system error, without disconnecting the
power.
Restart 1—The restart input function is only added in manual reset mode. The restart input turns on the OSSD
outputs after the blockage has been removed from the Safety Zone (and at startup).
Restart 1 Reset—This selection will perform on whichever input is needed at the moment (reset for faults, restart
for manual reset situations).
EDM—The EDM input function is only added if EDM is set to ON.
Muting Enable x—A mute enable input may be added if muting is enabled (Output Configuration settings).
Muting x x—Mute sensor inputs must be added if muting is enabled (Output Configuration settings).
Override x x—Override inputs must be added if the override function is enabled.
This parameter group assigns the signals of the input functions to the scanner pins. Each pin is also associated with
color-coded cable wiring, according to safety equipment regulations and standards. Previously assigned pins are
grayed out.
Click on the white > arrow in the upper right corner to move to the next configuration screen. Click on the white < to return to
the previous screen.
SX Safety Laser Scanner
www.bannerengineering.com - Tel: + 1 888 373 6767 87

Table of Contents

Related product manuals