9287500991 Rev K DECS-100 Introduction iii
REVISION HISTORY
The following information provides a historical summary of the changes made to the DECS-100
hardware, firmware, and software. The corresponding revisions made to this instruction manual
(9287500991) are also summarized. Revisions are listed in chronological order.
Hardware
Version and Date
Change
E, 01/01
Initial release
F, 05/01
Deepened potting shell
G, 10/01
Began supplying mounting screws
H, 02/02
SIL-PADS were added between power components and the heat sinks
Added manufacturing origin to the rear label
J, 07/02
Revised EEPROM
K, 02/03
Replaced transistor Q8B1 with an improved part
L, 03/03
Incremental improvements to firmware and BESTCOMS
M, 01/04
Improved flash memory retention
N, 05/05
Redesigned current transformer
Added front panel Underexcitation Limiting indicator
Enhanced EMI/RFI immunity
O
Version letter O not used
P, 08/06
Updated CD-ROM supplied with unit to include English and French
language instruction manuals
Q
Version letter Q not used
R, 04/07
Resolved UEL issue with firmware modification
S, 05/07
Provided German language manual on CD-ROM supplied with DECS-100
T, 07/07
Released firmware version 2.13.XX
U, 01/08
Improved power amplifier circuitry with more robust components
V, 03/08
Added Setpoint Auto Save feature
W, 03/09
Released BESTCOMS version 1.08.XX.
X, 02/10
Added enhancement for production testing.
Firmware
Version and Date
Change
1.09.XX, 01/01
Initial release
1.11.XX, 07/01
Enabled the protection function during the first 5 seconds of operation
Modified the OEL setpoint scale factor to be compatible with BESTCOMS
version 1.03.XX
Added the scale factor for per-unit gain
Established minimum voltage regulation at 30% of nominal sensing voltage
1.12.XX, 03/02
Added register to detect CT type
2.13.XX, 07/07
Added underexcitation limiting
Added takeover-style excitation limiting
Added bus voltage matching provisions
2.14.XX, 03/08
Added Setpoint Auto Save setting
BESTCOMS for
Windows
®
OS
Version and Date
Change
1.02.XX, 02/01
Initial Release
1.03.XX, 08/01
Changed OEL scale from 100 to 1,000 to match the change in firmware
version 1.11.01
Changed OEL default setting from 1 to 15
Changed the default for all protection functions to enabled
Add support for French regional settings
1.04.XX, 04/02
Made BESTCOMS compatible with older firmware versions