13-6 9440300990
Metering DECS-250
Control Panel
BESTCOMSPlus Navigation Path: Metering Explorer, Control Panel
HMI Navigation Path: Metering Explorer, Control Panel
The Control Panel (Figure 13-11) provides options for changing operating modes, selecting setpoint pre-
positions, fine tuning setpoints, and toggling virtual switches. The setpoints for AVR, FCR, FVR, var, and
PF are displayed, as well as Alarm status, PSS status, Null Balance status, and Grid Code Mode.
Figure 13-11. Control Panel
Start/Stop Mode: Two indicators show the start/stop mode of the DECS-250. When a mode is active, its
corresponding indicator changes from gray to green. To select the DECS-250 Start status, click the Start
button. Click the Stop button to select DECS-250 Stop status.
AVR/Manual Mode: AVR and Manual Mode status is reported by two indicators. When a mode is active,
its corresponding indicator changes from gray to green. AVR mode is selected by clicking the AVR button
and manual mode is selected by clicking the Manual button.
FCR/FVR Mode: FCR and FVR mode status is reported by two indicators. When a mode is active, its
corresponding indicator changes from gray to green. FCR mode is selected by clicking the FCR button
and FVR mode is selected by clicking the FVR button.
Var/PF Mode: Three indicators report whether Var mode, Power Factor mode, or neither mode is active.
When a mode is active, its corresponding indicator changes from gray to green. When neither mode is
active, the Off indicator changes from gray to green. Var mode is enabled by clicking the var button and
Power Factor mode is enabled by clicking the PF button. Neither mode is enabled by clicking the Off
button. Only one mode can be enabled at any time.
Setpoint Pre-position: A control button and indicator is provided for the three setpoint pre-positions.
Clicking the Set 1 button adjusts the excitation setpoint to the Pre-position 1 value and changes the Pre-
position 1 indicator to green. Pre-positions 2 and 3 are selected by clicking either the Set 2 or Set 3
button.