DECS-250 BESTlogic™Plus
Name Description Symbol
GCC
Disconnected
True when disconnection criteria for GCC has been
met and remains true until the GCC reconnect
timer expires.
GCC Freq High
Timing
True when the controlled generator’s frequency is
in the high frequency region for GCC and the timer
is active.
GCC Freq Low
Timing
True when the controlled generator’s frequency is
in the low frequency region for GCC and the timer
is active.
GCC Out of
Range Timing
True when the controlled generator’s frequency or
voltage are in the Out of Range region for GCC
and the timer is active.
GCC Timing For
Disconnect
True when any of the GCC timers is active.
GCC Timing for
Reconnect
True when the GCC reconnect timer is active.
GCC Voltage
High Timing
True when the controlled generator’s voltage is in
the high voltage region for GCC and the timer is
active.
GCC Voltage
Low Timing
True when the controlled generator’s voltage is in
the low voltage region for GCC and the timer is
active.
Gen Breaker Fail
to Open
The generator breaker did not open in the close
wait time period. (Available when the controller is
equipped with the optional Auto synchronizer, style
number xxxxAxx)
Gen Breaker Fail
to Close
The generator breaker did not close in the close
wait time period. (Available when the controller is
equipped with the optional Auto synchronizer, style
number xxxxAxx)
Gen Breaker
Sync Fail
True when generator breaker sync has failed.
(Available when the controller is equipped with the
optional Auto synchronizer, style number xxxxAxx)
Gen Dead True when the Generator Breaker Dead condition
settings have been exceeded. (Available when the
controller is equipped with the optional Auto
synchronizer, style number xxxxAxx)
Gen Failed True when the Generator Breaker Stable condition
settings are not met. (Available when the controller
is equipped with the optional Auto synchronizer,
style number xxxxAxx)
Gen Stable True when the Generator Breaker Stable condition
settings have been exceeded. (Available when the
controller is equipped with the optional Auto
synchronizer, style number xxxxAxx)
GOV Contact
Type Proportional
True when this option is selected. (Governor Bias
Control Settings screen)
Grid Code
Enabled
True when overall Grid Code functionality is
enabled.
KW Threshold
True when kW output is below the standard (non-
Grid Code) PF Active Power Level.