9440300990 28-15
DECS-250 Modbus
®
Communication
Group
Name
Register
Type
Bytes
R/W
Range
Contact Inputs
Stop Input
40910 bit 4
Uint16
2
R
True=1 False=0
Contact Inputs
Input 1
40910 bit 5
Uint16
2
R
True=1 False=0
Contact Inputs
Input 2
40910 bit 6
Uint16
2
R
True=1 False=0
Contact Inputs
Input 3
40910 bit 7
Uint16
2
R
True=1 False=0
Contact Inputs
Input 4
40910 bit 8
Uint16
2
R
True=1 False=0
Contact Inputs
Input 5
40910 bit 9
Uint16
2
R
True=1 False=0
Contact Inputs
Input 6
40910 bit 10
Uint16
2
R
True=1 False=0
Contact Inputs
Input 7
40910 bit 11
Uint16
2
R
True=1 False=0
Contact Inputs
Input 8
40910 bit 12
Uint16
2
R
True=1 False=0
Contact Inputs
Input 9
40910 bit 13
Uint16
2
R
True=1 False=0
Contact Inputs
Input 10
40910 bit 14
Uint16
2
R
True=1 False=0
Contact Inputs
Input 11
40910 bit 15
Uint16
2
R
True=1 False=0
Contact Inputs
Input 12
40911 bit 0
Uint16
2
R
True=1 False=0
Contact Inputs
Input 13
40911 bit 1
Uint16
2
R
True=1 False=0
Contact Inputs
Input 14
40911 bit 2
Uint16
2
R
True=1 False=0
Contact Outputs
Watchdog Output
40911 bit 3
Uint16
2
R
True=1 False=0
Contact Outputs
Output 1
40911 bit 4
Uint16
2
R
True=1 False=0
Contact Outputs
Output 2
40911 bit 5
Uint16
2
R
True=1 False=0
Contact Outputs
Output 3
40911 bit 6
Uint16
2
R
True=1 False=0
Contact Outputs
Output 4
40911 bit 7
Uint16
2
R
True=1 False=0
Contact Outputs
Output 5
40911 bit 8
Uint16
2
R
True=1 False=0
Contact Outputs
Output 6
40911 bit 9
Uint16
2
R
True=1 False=0
Contact Outputs
Output 7
40911 bit 10
Uint16
2
R
True=1 False=0
Contact Outputs
Output 8
40911 bit 11
Uint16
2
R
True=1 False=0
Contact Outputs
Output 9
40911 bit 12
Uint16
2
R
True=1 False=0
Contact Outputs
Output 10
40911 bit 13
Uint16
2
R
True=1 False=0
Contact Outputs
Output 11
40911 bit 14
Uint16
2
R
True=1 False=0
Virtual Switch
Virtual Switch 1
40911 bit 15
Uint16
2
R
True=1 False=0
Virtual Switch
Virtual Switch 2
40912 bit 0
Uint16
2
R
True=1 False=0
Virtual Switch
Virtual Switch 3
40912 bit 1
Uint16
2
R
True=1 False=0
Virtual Switch
Virtual Switch 4
40912 bit 2
Uint16
2
R
True=1 False=0
Virtual Switch
Virtual Switch 5
40912 bit 3
Uint16
2
R
True=1 False=0
Virtual Switch
Virtual Switch 6
40912 bit 4
Uint16
2
R
True=1 False=0
DECS Control
Manual FCR Only
40912 bit 5
Uint16
2
R
True=1 False=0
DECS Control
Droop Disable
40912 bit 6
Uint16
2
R
True=1 False=0
DECS Control
CC Disable
40912 bit 7
Uint16
2
R
True=1 False=0
DECS Control
Line Drop Disable
40912 bit 8
Uint16
2
R
True=1 False=0
DECS Control
Parallel Enable
40912 bit 9
Uint16
2
R
True=1 False=0
DECS Control
Soft Start Select Group 2
40912 bit 10
Uint16
2
R
True=1 False=0
DECS Control
PSS Select Group 2
40912 bit 11
Uint16
2
R
True=1 False=0
DECS Control
OEL Select Group 2
40912 bit 12
Uint16
2
R
True=1 False=0
DECS Control
UEL Select Group 2
40912 bit 13
Uint16
2
R
True=1 False=0
DECS Control
SCL Select Group 2
40912 bit 14
Uint16
2
R
True=1 False=0
DECS Control
Protect Select Group 2
40912 bit 15
Uint16
2
R
True=1 False=0
DECS Control
PID Select Group 2
40913 bit 0
Uint16
2
R
True=1 False=0
DECS Control
DECS Manual Auto
40913 bit 1
Uint16
2
R
True=1 False=0
DECS Control
Null Balance
40913 bit 2
Uint16
2
R
True=1 False=0
DECS Control
DECS Pre-position
40913 bit 3
Uint16
2
R
True=1 False=0
DECS Control
Var Limiter Select Group 2
40913 bit 4
Uint16
2
R
True=1 False=0
DECS Control
Var Active
40913 bit 5
Uint16
2
R
True=1 False=0
DECS Control
PF Active
40913 bit 6
Uint16
2
R
True=1 False=0