EasyManua.ls Logo

Basler DECS-250 - Page 308

Basler DECS-250
374 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29-32 9440300990
PROFIBUS Communication DECS-250
Instance Name
Inst. #
Type
RW
Key Name
Unit
Range
Config Protection 2
189
UINT32
R/W
Param Selection GG
No Unit
Gen VAB=0 Gen VBC=1 Gen
VCA=2 Gen V Average=3 Bus
Freq=4 Bus VAB=5 Bus VBC=6
Bus VCA=7 Gen Freq=8 Gen PF=9
KWH=10 KVARH=11 Gen IA=12
Gen IB=13 Gen IC=14 Gen I
Average=15 KW Total=16 KVA
Total=17 KVAR Total=18 EDM
Ripple=19 Exciter Field Voltage=20
Exciter Field Current=21 Auxiliary
Input Voltage=22 Auxiliary Input
Current (mA)=23 Setpoint
Position=24 Tracking Error=25 Neg
Seq V=26 Neg Seq I=27 Pos Seq
V=28 Pos Seq I=29 PSS
Output=30 Analog Input 1=31
Analog Input 2=32 Analog Input
3=33 Analog Input 4=34 Analog
Input 5=35 Analog Input 6=36
Analog Input 7=37 Analog Input
8=38 RTD Input 1=39 RTD Input
2=40 RTD Input 3=41 RTD Input
4=42 RTD Input 5=43 RTD Input
6=44 RTD Input 7=45 RTD Input
8=46 Thermocouple 1=47
Thermocouple 2=48 Power
Input=49 Network Load Share Error
Percent=50 Gen Scaled PF=51
APC Output=52 LVRT Output=53
Config Protection 2
189
UINT32
R/W
Stop Mode Inhibit GG
No Unit
NO=0 YES=1
Config Protection 2
189
UINT32
R/W
Threshold 1Type GG
No Unit
Disabled=0 Over=1 Under=2
Config Protection 2
189
UINT32
R/W
Threshold 2Type GG
No Unit
Disabled=0 Over=1 Under=2
Config Protection 2
189
UINT32
R/W
Threshold 3Type GG
No Unit
Disabled=0 Over=1 Under=2
Config Protection 2
189
UINT32
R/W
Threshold 4Type GG
No Unit
Disabled=0 Over=1 Under=2
Config Protection 2
190
Float
R/W
Hysteresis GG
%
0 - 100
Config Protection 2
190
Float
R/W
Arming Delay GG
Sec
0 - 300
Config Protection 2
190
Float
R/W
Threshold1Pickup GG
No Unit
-999999 - 999999
Config Protection 2
190
Float
R/W
Threshold 1
Activation Delay GG
Sec
0 - 300
Config Protection 2
190
Float
R/W
Threshold 2 Pickup GG
No Unit
-999999 - 999999
Config Protection 2
190
Float
R/W
Threshold 2
Activation Delay GG
Sec
0 - 300
Config Protection 2
190
Float
R/W
Threshold 3 Pickup GG
No Unit
-999999 - 999999
Config Protection 2
190
Float
R/W
Threshold 3
Activation Delay GG
Sec
0 - 300
Config Protection 2
190
Float
R/W
Threshold 4 Pickup GG
No Unit
-999999 - 999999
Config Protection 2
190
Float
R/W
Threshold 4
Activation Delay GG
Sec
0 - 300

Related product manuals