9440300990 29-31
DECS-250 PROFIBUS Communication
Instance Name
Inst. #
Type
RW
Key Name
Unit
Range
Exciter Diode Monitor
184
Float
R/W
Exciter Diode Inhibit
Threshold GG
%
0 - 100
Exciter Diode Monitor
184
Float
R/W
Exciter Open
Diode Pickup GG
%
0 - 100
Exciter Diode Monitor
184
Float
R/W
Exciter Open Diode
Time Delay GG
Sec
10 - 60
Exciter Diode Monitor
184
Float
R/W
Exciter Shorted
Diode Pickup GG
%
0 - 100
Exciter Diode Monitor
184
Float
R/W
Exciter Shorted Diode
Time Delay GG
Sec
5 - 30
Exciter Diode Monitor
184
Float
R/W
Exciter Pole Ratio GG
No Unit
1 - 10
Sync Check
185
UINT32
R/W
Mode GG
No Unit
Disabled=0 Enabled=1
Sync Check
186
Float
R/W
Phase Angle GG
Deg
1 - 99
Sync Check
186
Float
R/W
Slip Freq GG
Hz
0.01 - 0.5
Sync Check
186
Float
R/W
Volt Mag Error
Percent GG
%
0.1 - 50
Config Protection 1
187
UINT32
R/W
Param Selection GG
No Unit
Gen VAB=0 Gen VBC=1 Gen
VCA=2 Gen V Average=3 Bus
Freq=4 Bus VAB=5 Bus VBC=6
Bus VCA=7 Gen Freq=8 Gen PF=9
KWH=10 KVARH=11 Gen IA=12
Gen IB=13 Gen IC=14 Gen I
Average=15 KW Total=16 KVA
Total=17 KVAR Total=18 EDM
Ripple=19 Exciter Field Voltage=20
Exciter Field Current=21 Auxiliary
Input Voltage=22 Auxiliary Input
Current (mA)=23 Setpoint
Position=24 Tracking Error=25 Neg
Seq V=26 Neg Seq I=27 Pos Seq
V=28 Pos Seq I=29 PSS
Output=30 Analog Input 1=31
Analog Input 2=32 Analog Input
3=33 Analog Input 4=34 Analog
Input 5=35 Analog Input 6=36
Analog Input 7=37 Analog Input
8=38 RTD Input 1=39 RTD Input
2=40 RTD Input 3=41 RTD Input
4=42 RTD Input 5=43 RTD Input
6=44 RTD Input 7=45 RTD Input
8=46 Thermocouple 1=47
Thermocouple 2=48 Power
Input=49 Network Load Share Error
Percent=50 Gen Scaled PF=51
APC Output=52 LVRT Output=53
Config Protection 1
187
UINT32
R/W
Stop Mode Inhibit GG
No Unit
NO=0 YES=1
Config Protection 1
187
UINT32
R/W
Threshold 1 Type GG
No Unit
Disabled=0 Over=1 Under=2
Config Protection 1
187
UINT32
R/W
Threshold 2 Type GG
No Unit
Disabled=0 Over=1 Under=2
Config Protection 1
187
UINT32
R/W
Threshold 3 Type GG
No Unit
Disabled=0 Over=1 Under=2
Config Protection 1
187
UINT32
R/W
Threshold 4 Type GG
No Unit
Disabled=0 Over=1 Under=2
Config Protection 1
188
Float
R/W
Hysteresis GG
%
0 - 100
Config Protection 1
188
Float
R/W
Arming Delay GG
Sec
0 - 300
Config Protection 1
188
Float
R/W
Threshold 1 Pickup GG
No Unit
-999999 - 999999
Config Protection 1
188
Float
R/W
Threshold 1
Activation Delay GG
Sec
0 - 300
Config Protection 1
188
Float
R/W
Threshold 2 Pickup GG
No Unit
-999999 - 999999
Config Protection 1
188
Float
R/W
Threshold 2
Activation Delay GG
Sec
0 - 300
Config Protection 1
188
Float
R/W
Threshold 3 Pickup GG
No Unit
-999999 - 999999
Config Protection 1
188
Float
R/W
Threshold 3
Activation Delay GG
Sec
0 - 300
Config Protection 1
188
Float
R/W
Threshold 4 Pickup GG
No Unit
-999999 - 999999
Config Protection 1
188
Float
R/W
Threshold 4
Activation Delay GG
Sec
0 - 300