33-2 9440300990
Contact Expansion Module DECS-250
Type Tests
Shock
Withstands 15 G in 3 perpendicular planes.
Vibration
Swept over the following ranges for 12 sweeps in each of three mutually perpendicular planes with each
15-minute sweep consisting of the following:
5 to 29 to 5 Hz ............................ 1.5 G peak for 5 min.
29 to 52 to 29 Hz ........................ 0.036” Double Amplitude for 2.5 min.
52 to 500 to 52 Hz ...................... 5 G peak for 7.5 min.
HALT (Highly Accelerated Life Testing)
HALT is used by Basler Electric to prove that our products will provide the user with many years of
reliable service. HALT subjects the device to extremes in temperature, shock, and vibration to simulate
years of operation, but in a much shorter period span. HALT allows Basler Electric to evaluate all possible
design elements that will add to the life of this device. As an example of some of the extreme testing
conditions, the CEM-2020 was subjected to temperature tests (tested over a temperature range of –80°C
to +130°C),
vibration tests (of 5 to 50 G at +25°C), and temperature/vibration tests (tested at 10 to 20 G
over a temperature range of –60°C to +100°C). Combined temperature and vibration testing at these
extremes proves that the CEM-2020 is expected to provide long-term operation in a rugged environment.
Note that the vibration and temperature extremes listed in this paragraph are specific to HALT and do not
reflect recommended operation levels. These operational ratings are included in the Specifications
chapter of this manual.
Environment
Temperature
Operating ............................. –40 to +70°C (–40 to +158°F)
Storage ................................ –40 to +85°C (–40 to +185°F)
Humidity ..................................... IEC 68-2-38
Agency, Standards, and Directives
UL Approval
The CEM-2020 is a Recognized Component for the US and Canada under UL file E97035
(CCN-FTPM2/FTPM8) covered under the Standards below:
• UL 6200
• CSA C22.2 No.14-13
The CEM-2020 is a Recognized Component for the US and Canada under UL file E470837
(CCN-FTWD2/FTWD8) for use in Hazardous Locations:
• Class I Division 2
• Groups A, B, C & D
CSA Approval
The CEM-2020 is covered under CSA file 1042505 (LR23131-138S).
• CSA C22.2 No. 14-13
CE Compliance
This product complies with the requirements of the following EC Directives:
• Low Voltage Directive (LVD) 2014/35/EU
• Electromagnetic Compatibility (EMC) 2014/30/EU
• Hazardous Substances (RoHS 2) - 2011/65/EU