EasyManua.ls Logo

Basler DECS-250 - Page 41

Basler DECS-250
374 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9440300990 7-7
DECS-250 Regulation
voltage for a specific point on the line. Line drop compensation is applied to both the real and reactive
portion of the generator line current. It is expressed as a percentage of the generator terminal voltage.
Equation 7-1
is used to calculate the Line Drop Value.


=
󰇡

󰇣×

× cos 󰇡

󰇢󰇤󰇢
+ 󰇡×

× sin 󰇡

󰇢󰇢
Equation 7-1. Line Drop Value
LD
Value
= Line drop value (per unit)
V
avg
= Average voltage, metered value (per unit)
LD = Line Drop % / 100
I
avg
= Average Current, metered value (per unit)
I
bang
= Angle of phase B current (no compensation)
The LD
Value
is the per-unit value seen down the line from the synchronous machine. Equation 7-2 is used
to determine the voltage needed to adjust for line drop.
,
=
,


Equation 7-2. Voltage Needed to Adjust for Line Drop
Equation 7-3 is used to obtain primary units.

=
,
×

Equation 7-3. Obtain Primary Units
The new line drop adjusted setpoint is calculated using Equation 7-4.
 
=

+

Equation 7-4. Line Drop Adjusted Setpoint
Refer to Figure 7-5 for an illustration of the Line drop compensation settings.

Related product manuals