Commissioning
EL500x122 Version: 3.6
Fig.142: EL500x process data
• Terminal A, EL5001-0000-0001
only support for 1 status byte.
• Terminal B, EL5001-0000-1017
also existing process image (default).
• Terminal C, EL5001-0000-1017 with converted interface
In SyncManager 3 (inputs, blue) the PDO assignment of object 0x1A00 [}130] (default) was changed
to object 0x1A01 [}130], representing 2-byte status.
In addition the status word can be split into individually linkable bits under TwinCAT 2.11, so that the bit
references can be read in plain text during commissioning.
In order to see the subvariables in the online overview (D), mode "Show Sub Variables" must be
activated (E).
SubVariables and TwinCAT 2.10
Under TwinCAT 2.10 the consolidated representation of subvariables as shown for 16-bit status in
Fig. EL500x process data is not possible. Only the individually linkable bits are shown.