6 MK2430_D00129_01_Q_DEEN/01.2024
COMTRAXX® MK2430
Technical data
Insulation coordination acc. to IEC 60664-1
Rated insulation voltage ..................................................................AC 250 V
Rated impulse withstand voltage/pollution degree .......................... 4 kV/3
Supply voltage
Supply voltage U
S
......................................................................... AC/DC 24 V
Frequency range U
S
................................................................. 0/40…60 Hz
Operating range U
s
............................................... AC 18…28/DC 18…30 V
Power consumption ............................................................................ ≤ 3 VA
Voltage failure without reset .............................................................. ≤ 15 s
Interfaces
Interfaces .......................................................... RS-485 and USB (V2.0/V1.1)
Max. cable length in case of power supply of 1/2/3 MK2430
from one AN450
0.28 mm² (e.g. J-Y(St)Y n x 0.6) .................................................160/40/– m
0.5 mm² (e.g. J-Y(St)Y n x 0.8) .................................................. 250/70/– m
0.75 mm² ..................................................................................400/100/– m
1.5 mm² .................................................................................. 800/210/10 m
2.5 mm² ................................................................................ 1300/360/20 m
Max. cable length in case of power supply of 1/2/3 MK2430
from one AN410
0.28 mm² (e.g. J-Y(St)Y n x 0.6) ........................................... 300/150/100 m
0.5 mm² (e.g. J-Y(St)Y n x 0.8) ............................................ 500 /250/150 m
0.75 mm² .............................................................................. 750/375/250 m
1.5 mm² .............................................................................. 1500/750/500 m
2.5 mm² ............................................................................ 2500/1200/750 m
Switching elements (MK2430-11 only)
Number ........................................................................ 1 changeover contact
Function .................................................................................programmable
Operation mode ................................. N/C or N/O operation (programmable)
Electrical endurance, number of cycles ............................................... 10000
Contact data acc. to IEC 60947-5-1
Utilisation category ...............................................AC-13/ AC-14 /DC-12
Rated operational voltage .............................................. 24 V/24 V/24 V
Rated operational current .....................................................5 A/3 A/1 A
Minimum contact rating ......................................1 mA at AC/DC > 10 V
Connection
Connection ......................................................... pluggable screw terminals
Connection properties (supply voltage, BMS bus)
Connection of single conductors
rigid/flexible .................................................. 0.2…2.5/0.2…2.5 mm²
flexible with ferrule without/with plastic sleeve ...................................
.................................................................. 0.25…2.5/0.25…2.5 mm²
Multi-conductor connection (2 conductors of the same cross section)
rigid/flexible .................................................... 0.2…1/0.2…1.5 mm²
flexible with ferrule without plastic sleeve ...................... 0.25…1 mm²
flexible with TWIN ferrules with plastic sleeve ............... 0.5…1.5 mm²
Technische Daten
Isolationskoordination nach IEC 60664-1
Bemessungsspannung ..................................................................... AC 250 V
Bemessungs-Stoßspannung/Verschmutzungsgrad ............................4 kV/3
Versorgungsspannung
Versorgungsspannung U
s
............................................................. AC/DC 24 V
Frequenzbereich U
s
...................................................................0/40…60 Hz
Arbeitsbereich U
s
.................................................. AC 18…28/DC 18…30 V
Eigenverbrauch ................................................................................. ≤ 3 VA
Spannungsausfall ohne Reset ............................................................ ≤ 15 s
Schnittstellen
Schnittstellen .................................................. RS-485 und USB (V2.0/V1.1)
Max. Leitungslänge bei Versorgung von 1/2/3 MK2430
aus einem AN450
0,28 mm² (z. B. J-Y(St)Y n x 0,6) ................................................160/40/– m
0,5 mm² (z. B. J-Y(St)Y n x 0,8) ..................................................250/70/– m
0,75 mm² ..................................................................................400/100/– m
1,5 mm² ................................................................................. 800/210/10 m
2,5 mm² ................................................................................ 1300/360/20 m
Max. Leitungslänge bei Versorgung von 1/2/3 MK2430
aus einem AN410
0,28 mm² (z. B. J-Y(St)Y n x 0,6) .......................................... 300/150/100 m
0,5 mm² (z. B. J-Y(St)Y n x 0,8) ........................................... 500 /250/150 m
0,75 mm² .............................................................................. 750/375/250 m
1,5 mm² .............................................................................. 1500/750/500 m
2,5 mm² ............................................................................ 2500/1200/750 m
Schaltglieder (nur MK2430-11)
Anzahl .......................................................................................... 1 Wechsler
Funktion ..............................................................................programmierbar
Arbeitsweise ........................... Ruhestrom/ Arbeitsstrom (programmierbar)
Elektrische Lebensdauer bei Bemessungsbedingungen .. 10000 Schaltspiele
Kontaktdaten nach IEC 60947-5-1
Gebrauchskategorie ............................................... AC-13/ AC-14 /DC-12
Bemessungsbetriebsspannung ..................................... 24 V/24 V /24 V
Bemessungsbetriebsstrom ...................................................5 A/3 A/1 A
Minimale Kontaktbelastbarkeit ..........................1 mA bei AC/DC > 10 V
Anschluss
Anschlussart ...................................................... steckbare Schraubklemmen
Anschlussvermögen (Versorgungsspannung, BMS-Bus)
Einzelleiteranschluss
starr/flexibel .................................................. 0,2…2,5/0,2…2,5 mm²
flexibel mit Aderendhülse ohne/mit Kunststoffhülse .............................
.................................................................. 0,25…2,5/0,25…2,5 mm²
Mehrleiteranschluss (2 Leiter gleichen Querschnitts)
starr/flexibel .................................................... 0,2…1/0,2…1,5 mm²
flexibel mit Aderendhülse ohne Kunststoffhülse ............. 0,25…1 mm²
flexibel mit TWIN-Aderendhülse mit Kunststoffhülse .... 0,5…1,5 mm²

Other manuals for Bender COMTRAXX MK2430

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender COMTRAXX MK2430 and is the answer not in the manual?

Bender COMTRAXX MK2430 Specifications

General IconGeneral
BrandBender
ModelCOMTRAXX MK2430
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals