3. Function
3.1 Device features
AC/DC sensitive residual current monitor with external 35 mm measur-
ing current transformer
Can be used in conjunction with a contactor
Rated residual operating current I
Δn
= 6 mA acc. to UL943
Operating time acc. to UL943
r.m.s. value measurement, frequency range 0…150 Hz
Measured value display via multi-functional LCD
Alarm signalling via LEDs (TPD, ERR) and K2 changeover contact
Password protection to prevent unauthorised changes being made to
device settings
Permanent fault memory
N/C operation of alarm relay
Device test when the power supply voltage is connected
Automatic self test every 24 h
CT connection monitoring
Internal test circuit acc. to UL943 without additional external compo-
nents
External test and reset button can be connected
N-PE conductor monitoring on the load side
3.2 Description of function
The RCMA421H runs a device test when the power supply voltage is connect-
ed. During the start-up phase, the TRP LED lights up, the alarm LED ERR flashes
and the alarm relay switches to the alarm setting.
Once the device test has been completed successfully, the ERR alarm LED will
stop flashing, the TPD LED will go out and the alarm relay will return to the
normal setting.