Operation and setting
17
TGH1442en/06.2012
5.3 Menu structure
All adjustable parameters are listed in the columns "menu item" and "adjusta-
ble parameters". A display-like representation is used to illustrate the param-
eters in the column menu item. Different alarm categories can be assigned to
the alarm relays K1, K2 via the submenus r1, r2. This is done by activation or
deactivation of the respective function.
Menu
Sub
Menu
Menu
item
Activati
on
Adjustable parameter
AL
(response -
values)
> I2 - (Hi)
I
Δn2
(Alarm 2)
> I1 - (Hi)
I
Δn1
as % of I
Δn2
(Alarm 1, prewarning)
Hys -
Hysteresis I
Δn1
/ I
Δn2
out
(output con-
trol)
M ON Fault memory (on/off/con)
1
- Operating mode K1 (n.c.)
2
- Operating mode K2 (n.c.)
RL -
Reload function (memory =
off)
r1
(K1: (assign-
ment alarm
category)
1 Err ON Device error at K1
r1 I1 off
Prewarning I
Δn1
at K1
r1 I2 ON
Alarm I
Δn2
at K1
1 tES ON Device test
r2
(K2: (assign-
ment alarm
category)
2 Err ON Device error at K2
r2 I1 off
Prewarning I
Δn1
at K2
r2 I2 ON
Alarm I
Δn2
at K2
2 tES ON Device test

Other manuals for Bender RCMA423

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender RCMA423 and is the answer not in the manual?

Bender RCMA423 Specifications

General IconGeneral
BrandBender
ModelRCMA423
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals