Technical data
36
TGH1442en/06.2012
6.4 Error codes
Should, contrary to all expectations, a device error occur, error codes will ap-
pear on the display. Typical error codes are described below:
Error code Meaning:
E.01
Fault CT connection monitoring
Appropriate action:
Check CT connection for short-circuit or inter-
ruption. After eliminating the fault, the error
code will be automatically deleted.
E.02
Fault CT connection monitoring
during manual self test.
Appropriate action:
Check CT connection for short-circuit or inter-
ruption. After eliminating the fault, the error
code will be automatically deleted.
E....
Appropriate action when error codes > 02
occur:
Appropriate action:
Carry out a reset. Reset the device to factory
setting. After eliminating the fault, the error
code will be automatically deleted.
If the fault continues to exist, please contact the
Bender Service.