Operation and setting
30
TGH1442en/06.2012
5.6 Commissioning
Prior to commissioning, check proper connection of the residual current
monitor.
5.7 Factory setting
Response value overcurrent I1 (prewarn-
ing)
Response value overcurrent I2 (alarm)
Hysteresis:
Fault memory M:
Operating mode K1/K2
Start-up delay:
Response delay:
Delay on release:
Password:
15 mA (50 % of I2)
30 mA
15 %
activated (on)
N/C operation (n.c.)
t = 0.5 s
t
on1
= 1 s
t
on2
= 0 s
t
off
= 1 s
0, deactivated (Off)