TYPES VRA065 VRA090 VRA110 VRA140 VRA170 VRA220 VRA285
Heat Input kW 21 28 35 45 55 71 92
Heat Output kW 19,5 25,5 31,5 40,5 50 64,4 84
Efficiency % 92.8 91.1 90.0 90.0 91.0 90.7 91.3
No Fans 1 1 1 1 1 1 2
Airflow @ 15 °C
Airflow @ 50 °C
m
3
/h
1 450
1 625
2 050
2 250
2 900
3 250
4 000
4 400
4 900
5 400
5 800
6 400
8 000
8 800
Delta T °C 40 36 32 30 30 32 32
Axial fan throw m 12 16 23 26 28 30 30
Gas rate @ 15°C
Natural G20
Propane G31
20 mbar
37 mbar
2.22 m
3
/ h
1.64 kg/h
2.96 m
3
/ h
2.18 kg/h
3.70 m
3
/ h
2.73 kg/h
4.76 m
3
/ h
3.51 kg/h
5.82 m
3
/ h
4.30 kg/h
7.40 m
3
/ h
5.46 kg/h
10.0 m
3
/ h
7.40 kg/h
Flue diameter mm
80 /125 80/125
100 130 130 130
Comb air diameter mm 100 130 130 130
Electrical Supply V 230 volts 1ph 50Hz
Running Current A 1.3 1.3 1.4 1.5 2.2 2.5 3.2
Weight kg 82 82 90 105 127 145 185
Sound level @ 5M
dBa 39 40 41 46 51 51 49
80/125
Fan Speed 900 900 900 900 1400 1400 900
Tr/m
Technical Data VRA
Dimensional Data VRA
Model VRA
Models VRA are Room Sealed
Axial fan with vertical and horizontal
louvres as standard and are
unsuitable for ducted systems
VRA
A B C
Ø
Flue
Ø
Air
Ø
Gas
065
1040 800 460 80 / 125 1/2
090
1040 820 460 80 / 125 1/2
110
1040 820 510 1/2
140
1040 820 570 100 100 1/2
170
1040 840 700 130 130 1/2
220
1120 840 825 130 130 3/4
285
1120 840 1075 130 130 3/4
80 / 125
2–1 TECHNICAL SPECIFICATIONS
Connections 140/170/220/285
Flue-
Gas
Air
Connections 65/90/110