2-2Technical Data VRC
Dimensional Data :
TYPES VRC065 VRC090 VRC110 VRC140 VRC170
Heat Input kW 21 28 35 45 55
Heat Output kW 19,5 25,5 31,5 40,5 50
Efficiency % 92.8 91.1 90.0 90.0 90.7
Fan speed Tr/m 1 400 1 400 1 400 1 400 1 400
Airflow @ 15 °C
Airflow @ 50 °C
m
3
/h
1 450
1 625
2 050
2 250
2 900
3 250
4 000
4 400
4 900
5 400
Delta T °C 40 36 32 30 30
Available outlet pressure mm CE 10 10 10 10 10
Gas rate @ 15°C
Natural G20
Propane G31
20 mbar
37 mbar
2.22 m
3
/ h
1.64 kg/h
2.96 m
3
/ h
2.18 kg/h
3.70 m
3
/ h
2.73 kg/h
4.76 m
3
/ h
3.51 kg/h
5.82 m
3
/ h
4.30 kg/h
Flue diameter mm
80 / 125 80 / 125 80 / 125
100 130
Combustion air diameter mm 100 130
Electrical supply 230 volts / 1ph / 50Hz
Running current A 3.8 4.0 4.0 5.5 6.0
Weight kg 97 97 105 120 147
Model VRC
Models in the VRC range are room sealed with
Centrifugal Fan suitable for ducted systems
(Vertical and Horizontal louvres optional)
VRC
A C D L Ø F
Ø
Air
Ø
Gas
065
1040 460 1160 360 80 / 125 1/2
090
1040 460 1160 360 80 / 125 1/2
110
1040 510 1160 410 80 / 125 1/2
140
1040 570 1260 470 100 100 1/2
170
1040 700 1260 600 130 130 1/2
Connections 65/90/110
Connections 140/170
Flue
Flue
Gas
Gas