19 Bentone
5.3 Setting of brake disc and air flow
Prior to commissioning, the basic settings of the burner can be set in
accordance with the diagram, see Basic settings. Note that it is simply a
matter of a basic setting that should be adjusted retrospectively once
the burner has started. A flue gas analysis and soot quantity measurement
must be carried out when fine-tuning the burner.
Grade of Oil Excess air flue gases Max. % CO
2
% O
2
% CO
2
Lambda 1.2
Light oil, B10 heating oil/
biofuel blend (as defined
in DIN V51603-6)
4±1 ≈12,5 15,4
Recommended excess air