EasyManua.ls Logo

Berges ACM-D2 2.2kW - Page 49

Default Icon
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function SW4: Fmin configuration
TAB3
This function defines the inverter behaviour at Fmin. Two different settings are possi-
ble (see the following diagramm).
SUB XPAR
Range: ON, OFF
Default: ON
Function SW5: Error signalling relay configuration
TAB3
This function defines when the fault relay ( term. 122,123,124) becomes active.
ON: Fault relais becomes active on fault or when the inverter is disabled.
OFF: Fault relais becomes active only on fault.
SUB XPAR
Range: ON, OFF
Default: ON
Function SW6: DC - Brake trigger
TAB3
ON: The DC-brake is activated automatically if the output frequency sinks
below the frequency threshold 1 (TAB1, funct. U) and the setpoint input
value is zero or manually by activating term. 30.
OFF: The DC-brake is ON if terminal is activated.
Indication: For the RESET to the DC-brake see configuration in TAB3,
SUBXPAR, function SW1.
SUB XPAR
Range: ON, OFF
Default: OFF
Function SW7: Autostart
TAB3
This function defines the start condition for line start (POWER-ON).
ON: With this setting, the inverter will turn on when the line power is applied and
the ENABLE and START/STOP-command is present.
OFF: Line start lockout. The inverter will not start upon application of the line
power. START/STOP or ENABLE must be opened, then closed to
start the drive.
SUB XPAR
Range: ON, OFF
Default: ON
SW4 ON
Fmin : Value TAB1, function 4.
f : Output frequency.
Speed ref. : Speed reference value.
SW5 ON
SW6 OFF
SW7 ON
BERGES electronic
29.05.98 Operating manual ACM-D2 47

Table of Contents