Be242 Be242RB Be242-22 OEM's Manual V4.X.XX - March - 2023 page 14
14
Table 7.03A - ENGINE PARAMETERS Note: [ xx " ] = seconds, [ xx ' ] = minutes, [ oFF ] = disabled
Parameter Code & Description
Default
Min
Max
Options
P.19
Crank delay (it delays the cranking)
[ 2" ]
0
15 secs
-
P.20
Crank time (maximum cranking time if the
engine fails to start during the attempt)
[ 5" ]
1 sec
15 secs
-
P.21
Rest time (pause of time between starting
attempts)
[ 5" ]
3 secs
15 secs
-
P.22
Pre-glow time (see ‘Modes’ for the mode of
operation. (Push F1)
[ oFF ]
1 sec
59 mins
[ oFF ]
Modes as indicated below (Push F2)
[ 1 ]
-
-
1-2-3-4
Starting Motor Total rest timing
Pre-glow mode 1
Pre-glow mode 2
Pre-glow mode 3
[ P.21 ]
[ P.20 ]
[ P.22 ]
[ P.22 ]
[ P.26]..27]..28 ]
[ P.22 ]
Pre-glow mode 4 (Choke)
Total rest timing
Crank termination (engine running detect)
P.23
Engine Warm-up time
[ 15" ]
0
59 mins
-
P.24
Engine Cooling time
[ 15" ]
0
59 mins
-
P.25
Stop Solenoid timing (Energized to stop)
[ 5" ]
1 sec
59 mins
-
P.26
Alternator Crank termination (Push F1)
[ oFF ]
3.0 V
30.0 V
[oFF]
Belt break setting (Push F2)
[ oFF ]
3.0 V
30.0 V
[oFF]
P.27
Crank termination setting (Generator Voltage)
[ 100 ]
60 V
998 V
[oFF]
P.28
Crank termination (Generator Frequency)
[30.0]
20.0 Hz
70.0 Hz
[oFF]
Table 7.03B - ENGINE PARAMETERS Note: [ xx " ] = seconds, [ xx ' ] = minutes, [ oFF ] = disabled
Parameter Code & Description
Default
Min
Max
Options
29-30
NOT USED
[ oFF ]
P.31
Crank attempts (numbers)
[ 3 ]
3
15
-
P.32
Purge timing (for Gas fuelled engine)
[ 1" ]
1 sec
15 secs
-