EasyManua.ls Logo

Binder redLINE RF 53 - Automatic Mode Set-Point Entry

Default Icon
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Redline Operating Manual RE / RF / RI 12/2010 page 29/46
6.2 Operating mode Automatic Mode – entering the set-point
The main menu display indicates on top the actual temperature value and below the temperature set-
point. If the set-point is higher then the actual value, the actual value is controlled to the set-point.
Main menu (Automatic):
heating on, adjusting to
the set-point
Main menu (Automatic):
heating off, equilibrated
state
or
There are two different ways to enter the temperature set-point:
1. In the operating mode “Automatic Mode”, enter the set-point directly in the main menu using the arrow
keys.
Main menu (Automatic) Main menu (Automatic)
several
times
2. Toggle to the set-point setting menu via the functional button. Enter the set-point using the arrow keys.
Main menu
(e.g. Automatic)
Setting menu for
temperature set-point
Setting menu for
temperature set-point
several
times
SETPOINT 1 SETPOINT 1
Back to the main menu display: press the functional button 4 times or wait for 1 minute.
Main menu (Automatic)
4 x
Now the controller operates continuously with the entered set-point until cancellation. The heating is
active (Heating pilot lamp lit or flashing).

Table of Contents

Related product manuals