ANTSPACE HK3 Water cooling container & Dry-Wet Tower Product Manual
67
Type
Causes
Solution
Remarks
Noise
and
abnormal
noise
1: Water pump
cavitation
Check the pressure on the Water inlet side
(return pressure or pressure gauge) and
replenish the Water in a timely manner
2: Pump shaft
connection issue
Check the mechanical connection of the
pump shaft
3: Insufficient
lubrication of
motor shaft
Adding lubricating oil
4: Safety valve
action
Check if there is too much Water in the
water tank, unable to release pressure in a
timely manner, and discharge excess
Water from the water tank
Water
pump
shaft seal
leakage
Replace the water pump shaft seal