ANTSPACE HK3 Water cooling container & Dry-Wet Tower Product Manual
66
High
environmental
humidity
After the on-site operation and
maintenance personnel see the alarm
message, they only need to increase the
target value of the supply Water
temperature by 5℃ to prevent
condensation.
The logic set in the
program is: when the
dew point
temperature value is
greater than the
supply Water
temperature value -
5℃, the system will
prompt a
condensation alarm
Pressure
display
fluctuate
s
1: There is air in
the system
Please ask on-site operation and
maintenance personnel to open the exhaust
valve for exhaust
If the return pressure is lower than the set
value, the replenishment pump will
automatically replenish the system
Check the wiring circuit of the pressure
sensor and tighten it
3: The PLC
acquisition
channel is
damaged
Replace the module corresponding to the
PLC sensor.
The
pump is
running,
but the
flow rate
is
insufficie
nt
1: There is air at
the water pump
suction port
Open the exhaust port above the water
pump suction port with a wrench, wait
until there is even Water flowing out, and
repeat 2-3 times (refer to the user manual
for specific operations)
3: Insufficient
system coolant
(low return
pressure)
Under live conditions, use a multimeter to
check the power supply of the fan and
tighten it when power is cut off.
3: Circuit
breaker tripped
Close the circuit breaker