ANTSPACE HK3 Water cooling container & Dry-Wet Tower Product Manual
65
Type
Causes
Solution
Remarks
High
Water
supply
temperat
ure alarm
After the high
Water supply
temperature
alarm occurred,
the operation
and maintenance
personnel did
not handle it in a
timely manner,
resulting in a
continuous
increase in the
Water supply
temperature
Before identifying the cause, it is possible
to consider shutting down some high
computing power servers, reducing the
load, and then finding the cause of the
high Water supply temperature alarm.
The alarm value for high Water supply
temperature can be set on the screen as
needed.
High
Water
supply
pressure
alarm
1: Filter clogged
Clean the filter element
2: Water supply
and return valve
malfunction or
incomplete
opening
Open the Water supply and return valves
3: Pressure
sensor failure
Replace the pressure sensor
Low
return
Water
pressure
alarm
1: Insufficient
cooling Water in
the water tank
Replenish the water tank with cooling
Water
2:
Replenishment
pump failure
Check the cause of the malfunction of the
replenishment pump
3: Pressure
sensor failure
Replace the pressure sensor
4: Leakage
Check for system leaks
Low
Water
supply
flow
alarm
1: Water supply
and return valve
malfunction or
incomplete
opening
Open the Water supply and return valve
2: Dirty and
clogged filter
Clean the filter element
3: Flow sensor
failure
Replace the flow sensor
4: Leakage
Check for system leaks