ANTSPACE HK3 Water cooling container & Dry-Wet Tower Product Manual
64
Cold
tower
Water
level low
alarm
The water level
inside the
cooling tower
decreases
Timely replenish the cooling tower and
reset the fault
After a low Water
level alarm in the
cooling tower
occurs, the system
starts timing. After
about 50 minutes,
the spray pump stops
spraying. To avoid
overheating of the
high computing
power server due to
the spray pump
stopping spraying,
on-site operation and
maintenance
personnel are
requested to
replenish the Water
in a timely manner
after seeing the
alarm.
High
Water
supply
temperat
ure alarm
1: Cooling fan
not running
Check whether the fan operates normally
and whether the power supply circuit of
the fan is normal
2: Spray pump
not running
Check whether the spray pump operates
normally and whether the power supply
circuit of the spray pump is normal
3: Temperature
sensor damaged
Replace the temperature sensor. The alarm
value for high Water supply temperature
can be set on the screen as needed
4: Abnormal
water level in the
cooling tower
Check the water level of the cooling tower
to ensure normal water replenishment