ANTSPACE HK3 Water cooling container & Dry-Wet Tower Product Manual
63
Type
Causes
Solution
Remarks
Spray
pump
failure
Dirty and
clogged filter at
the water tank
suction port
causing overload
1: Turn off the circuit breaker (QFWCU)
in the main control cabinet first.
2: Reset VF03 in the cooling tower control
cabinet (manually turn the knob of the
motor protector to the vertical position,
that is, switch on).
3: Check if the filter in the cooling tower
water tank is dirty or blocked, and clean it
after it is dirty or blocked
4: After troubleshooting, reference Figure
7-30 press the right reset button.
5Start the spray pump after an interval
of 2-3 minutes.
Warning: after the
system is powered
on, the spray pump
cannot idle when
there is no Water in
the system
1#
cooling
fan
failure
The current of
the exhaust fan
is too high, and
there may be
strips in the fan
blades that
hinder the
operation of the
fan
1: Turn off the circuit breaker (QFVF02)
in the main control cabinet first.
2: If there are debris in the fan blades, first
clean them up; If there are no debris and
there is no reason for fan failure, the
manufacturer needs to be contacted.
3: Reset the motor protector in the main
control cabinet (1# fan corresponds to
QFG01; 2# fan corresponds to QFG02; 3#
fan corresponds to QFG03) (manually turn
the knob of the motor protector to the
vertical position, which means that it is
closed).
4: After troubleshooting, reference Figure
7-30 press the right reset button.
5: After an interval of 2-3 minutes, turn on
the cooling fan again.
2#
cooling
fan
failure
3#
cooling
fan
failure
Leakage
alarm
There is Water
leakage from the
inlet and outlet
of the high
computing
power server to
the floor, wetting
the leakage
sensor.
1: Find areas on the floor where there is
Water.
2: Above this area, carefully search for any
leakage from the inlet and outlet of the
high computing power server.
3: After finding the leaking area, handle it
by replacing the quick plug and corrugated
pipe, then clean the leaking site and wipe
the leaking monitoring tape dry.