ANTSPACE HK3 Water cooling container & Dry-Wet Tower Product Manual
52
execute in the order of automatic control logic.
When you need to close, click on 'STOP' on the Home interface.
3) Manual Control Interface
When the device needs to be debugged with Water, it is necessary to adjust the device control
mode to the "MC" position, and then enter the "manual control" screen, as shown in the following
figure:
Figure 7-30 Manual control interface
At this point, the motor and frequency converter to be operated can be started by jogging. In
general, when the system needs to add Water, it is necessary to manually start and corresponding
electric valves, make-up pumps, and circulation pumps. However, before starting, it is necessary to
ensure that the motor runs in the correct direction.
Therefore, after powering on, turn on the 1 # exhaust fan and observe its running direction. When
the wind blows out of the container, it indicates positive rotation. Before the equipment leaves the
factory, all motors have been debugged and turned forward. Therefore, it is only necessary to observe
the operating status of one motor. When the motor reverses, it is necessary to adjust the phase of the
three-phase power input of QFWCU, that is, change the phase sequence of the two cables.
4) Parameter Setting Interface