72
Figure 9-3 Location of discharge ball valve in pump station
5) Water Tank Level Inspection
The system monitors the Water levels in two water tanks (inside the container and in the cooling
tower). When the Water level in the water tank falls below the required value, the system touch screen
will give an alarm indicating that the water tank level is low. At this time, it is necessary to promptly
check for faults and replenish the coolant.
Even if there is no alarm for the water tank level, it should be checked regularly on a daily basis:
The Water level in the water tank inside the container needs to be checked once a week after
stable operation. If the water tank does not reach 2/3 of the limit, it needs to be replenished in a timely
manner.
The Water level of the cooling tower water tank is required to be checked once a day, and water
shutdown is not allowed (unless dry cooling mode is adopted in winter, at which time the internal
water of the cooling tower needs to be drained).